What is the required kVA rating of transformer that must handle a maximum load current of 8 A with a secondary voltage of 2 kV?

By BYJU'S Exam Prep

Updated on: September 25th, 2023

What is the required kVA rating of transformer that must handle a maximum load current of 8 A with a secondary voltage of 2 kV?

  1. 4 kVA
  2. 0.25 kVA
  3. 16 kVA
  4. 8 kVA

Answer: Option C. 16 kVA

The required kVA rating of transformer that must handle a maximum load current of 8 A with a secondary voltage of 2 kV is 16kVA.

Solution

Given,

Maximum secondary load current I2,max= 8 A,

Rated secondary voltage V2 = 2 kV,

So, kVA rating of transformer = 2 kV × 8 A

= 16 kVA.

Therefore, the required kVA rating of transformer that must handle a maximum load current of 8 A with a secondary voltage of 2 kV is 16kVA.