Time Left - 15:00 mins
GATE 2024 Power System Rank Booster Quiz 9
Attempt now to get your rank among 32 students!
Question 1
The line impedances of 3-phase, transmission line are Zaa = j50Ω, Zab = j10Ω, Znn = j80Ω, Zan = j15Ω. Calculate the self and mutual impedance of the system as well as sequence impedances of the system.
(1) Zs = j50Ω, Zm = j10Ω, Z(0) = j80Ω
(2) Zs = j100Ω, Z(0) = j220Ω
(3) Zm = j60Ω, Z(1) = Z(2) = j40
(4) Zm = j10Ω, Z(1) = j40
Question 2
In a large, interconnected power system, consider three buses having short circuits capacities: (1) 2000 MVA, (2) 1500 MVA and (3) 1200 MVA respectively. The voltage of all the buses are 1 p.u. If a three-phase fault takes place on bus ‘2’, the change in bus voltage is described as
Question 3
A 6.6 kV, 3-phase, 10 MVA alternator has positive, negative and zero sequence reactance as j0.1 p.u, j0.05 p.u and j0.045 p.u. A double line to ground fault occurs, then the magnitude of positive sequence voltage is _______.
Question 4
An alternator is having self-inductance of the winding j0.1 p.u. and mutual inductance is j0.03 p.u. The sequence impedances are:
(1) Zg(0) = 0.07 p.u. = 0.04 p.u.
(2) Zg(1) = Zg(2) = 0.07 p.u. Zg(0) = 0.16 p.u. = 0.13 p.u.
(3) Zg(0) = 0.04 p.u. = 0.13 p.u.
(4) Zg(1) = Zg(2) = 0.13
Question 5
There are three generator connected in parallel for each positive, negative, zero sequence reactance are 0.5 p.u, 0.4 p.u and 0.25 p.u respectively. For pre-fault voltage of 1 p.u, single line to ground fault current magnitude if fault is occurred at terminal of generator is ________.
Question 6
The zero-sequence circuit of a three-phase transformer as shown in figure below is
Question 7
A 45 MVA, 13.2 kV alternator with solidly grounded neutral has a sub-transient reactance of 0.25 p.u. The negative and zero sequence reactance’s are 0.35 p.u. and 0.1 p.u. respectively. A single line to ground fault occurs at the terminals of an unloaded alternator the fault current is ________.
- 32 attempts
- 0 upvotes
- 0 comments
Nov 16ESE & GATE EE