ESE 2021 Technical Quiz || Measurement of Power & Energy, Power Factor
Attempt now to get your rank among 255 students!
Question 1
There will be serious errors if power factor of non-sinusoidal waveform is measured by electrodynamometer power factor meter. This is true for
Question 2
The meter constant of single phase 220 V Induction type wattmeter is 500 rev/kWh. The speed of the meter disc for a current of 10 A at 0.8 power factor lagging will be
Question 3
A single phase energy meter of the induction type is rated 230 V, 10 A, 50 Hz and has a meter constant of 600 rev/kWhr when currently adjusted. If quadrature adjustment is slightly disturbed so that the lag is 85°, calculate the percentage error of full load, 0.8 pf lag?
Question 4
The voltage flux adjustment in a certain single phase 200 V induction watt-hour meter is altered so that the phase angle between the applied voltage and the flux is due to it is 85⁰. Find the % error in the reading when current through the meter is 6 A at 0.75 lagging power factor.
Question 5
A 230 V, 10 A, 1-ϕ energy meter makes 90 revolution in 3 minutes at half load rated voltage and unity power factor. If meter constant is 1800 rev/kWh. Then error at half load will be